Measurement and protection
Measuring transducer and protection device for single- and three-phase power systems.
-
- connect a PLC via CAN bus
- use relays to push commands and to control a breaker
Measurement
easYprotec 1410 | MFR300 | |
---|---|---|
Functions | ||
3 true RMS voltage inputs | ||
3 true RMS current inputs | ||
Class 0.5 measurement accuracy | ||
Configurable trip/control setpoints | ||
Configurable delay timers for individual alarms (0.02 to 300.00 s) | ||
4 configurable relays (change-over) | 2 | 4 |
1 “Ready for operation” relay | ||
Switchable relay logic | ||
2 kWh counters (max. 1012 kWh) | ||
2 kvarh counters (max. 1012 kvarh) | ||
CANopen / Modbus communication | ||
Configurable via CAN bus / RS-485 / Service Port (USB/RS-232) | ||
Configurable via Service Port (USB / RS-232) | ||
Protection | ||
Over-/undervoltage (59/27) | ||
Over-/underfrequency (81O/U) | ||
Voltage asymmetry (47) | ||
Overload (32) | ||
Positive/negative load (32R/F) | ||
Unbalanced load (46) | ||
Phase shift (78) | ||
Overcurrent (50/51) | ||
df/dt (ROCOF) | ||
Ground fault | ||
QV monitoring | ||
Voltage increase | ||
Freely configurable time-dependent undervoltage monitoring for: FRT (fault ride-through) |
MFR-300 Multifunction Relay / Measuring Transducer with CANopen / Modbus Communication
The MFR 300 is a measuring transducer for monitoring single- and three-phase power systems. The MFR 300 has both voltage and current inputs for measuring an electrical power source. A digital processor makes it possible to accurately to measure true RMS values, regardless of harmonics, transients or disturbing pulses. The primary measured and calculated values are transmitted via CANopen / Modbus protocol to a supervisory control system.
The MFR 300 performs monitoring functions for mains decoupling, including four freely configurable time-dependent undervoltage monitoring functions for FRT (fault ride-through).
The primary measured values of voltage and current are used to calculate the real, reactive, and apparent power and the power factor (cosphi) values.
Accessories
![Configuration Software Configuration Software](https://easygen.org/wp-content/uploads/2022/03/accessories4.webp)
Toolkit
configuration via Woodward’s standard Software Toolkit.
![usbCable USB](https://easygen.org/wp-content/uploads/2022/03/usbCable.webp)
USB configuration interface
USB port configuration interface. The PC/laptop side is seperated from the Woodward unit side through galvanic isolation.
part number: 5417-1251